HVAC & Heat Pump Circuit Calculator

Calculate Minimum Circuit Ampacity (MCA), Maximum Overcurrent Protective Device (MOCP), and wire sizing for AC & heat pumps per NEC Article 440.

NEC edition

Inputs

Amps
Amps
kW
Amps
Amps

VoltageLab app

Take this toolkit with you on the job

The full VoltageLab electrician app — wire tables, code lookups and job-site calculators offline, on Android and iOS.

⚡ Test your knowledge
NEC Article 220 was renumbered in the 2026 code cycle. What is the new article number?
  • A. Art. 100
  • B. Art. 120
  • C. Art. 200
  • D. Art. 230
💡 NEC 2026 renumbered Article 220 (Branch-Circuit, Feeder, and Service Calculations) to Article 120.
Energy Management Systems were moved from Article 750 to which article in NEC 2026?
  • A. Art. 100
  • B. Art. 125
  • C. Art. 130
  • D. Art. 150
💡 NEC 2026 moved Energy Management Systems from Article 750 to Article 130.
Which NEC standard size overcurrent device comes after 90A?
  • A. 95A
  • B. 100A
  • C. 110A
  • D. 105A
💡 Per NEC §240.6(A), the standard sizes are …90, 100, 110, 125… There is no 95A standard size.

VoltageLab app

Studying for your electrical exam?

Practice NEC exam questions with full explanations and progress tracking, right on your phone.

How it works & the NEC rules behind it

Air conditioning and heat pump systems are governed by NEC Article 440, which provides specialized rules distinct from standard Article 430 motor circuits. Equipment nameplates provide two critical engineering parameters: MCA and MOCP.

Core Sizing Rules (NEC Article 440):

  • 1. Minimum Circuit Ampacity (MCA, §440.33): Defines the minimum conductor current carrying capacity:
    MCA = (1.25 × Compressor RLA) + Fan Motor FLA + Auxiliary Heat Amps.
    Conductors are sized from NEC Table 310.16 to carry at least the MCA.
  • 2. Maximum Overcurrent Protective Device (MOCP, §440.22): Protects against short circuits and ground faults without tripping on compressor startup:
    MOCP = (1.75 × Compressor RLA) + Fan Motor FLA.
    Where the calculated value does not correspond to a standard size, the next lower standard size is used, or up to 225% RLA if the 175% breaker trips on inrush (§440.22(A) Exception).
  • 3. Breaker Larger Than Wire (§440.6): Unlike general branch circuits (§240.4(D)), it is standard and code-compliant in HVAC circuits for the circuit breaker (MOCP) to be rated higher than the wire ampacity, because the compressor has internal thermal overload protection.
  • 4. Disconnect Switch Rating (§440.12): Must be rated for not less than 115% of total nameplate current and located within sight of the equipment (§440.14).

Formulas & equations

MCA = (Compressor RLA × 1.25) + Fan FLA + Auxiliary Heat Amps (§440.33) Standard MOCP = (Compressor RLA × 1.75) + Fan FLA (§440.22(A)) Max Allowed MOCP (Startup Inrush) = (Compressor RLA × 2.25) + Fan FLA (§440.22(A) Ex.) Disconnect Minimum Amps = (Compressor RLA + Fan FLA) × 1.15 (§440.12)

NEC reference table

Heat Pump / AC Tonnage Typical Compressor RLA Typical Fan FLA Calculated MCA Recommended Wire & MOCP
1.5 Ton (18k BTU)9.0 A0.8 A12.1 A#14 AWG Cu / 20A Breaker
2.0 Ton (24k BTU)12.0 A1.1 A16.1 A#12 AWG Cu / 25A Breaker
3.0 Ton (36k BTU)16.7 A1.5 A22.4 A#10 AWG Cu / 35A Breaker
4.0 Ton (48k BTU)21.8 A1.8 A29.1 A#10 AWG Cu / 45A Breaker
5.0 Ton (60k BTU)26.4 A2.4 A35.4 A#8 AWG Cu / 50A Breaker

Worked example, step by step

Example: Sizing 3-Ton Heat Pump Outdoor Condenser Unit

Nameplate: 240V 1-Phase, Compressor RLA = 16.7A, Outdoor Fan FLA = 1.5A.

  • 1. Calculate MCA: (16.7A × 1.25) + 1.5A = 20.88 + 1.5 = 22.38 Amps.
  • 2. Conductor Sizing: Per Table 310.16 (75°C Copper), #10 AWG THHN (rated 35A) is required (since #12 is 20A @ 60°C).
  • 3. Calculate MOCP: (16.7A × 1.75) + 1.5A = 29.23 + 1.5 = 30.73 Amps → Standard 30A or 35A HVAC Circuit Breaker.
  • 4. Disconnect Switch: (16.7 + 1.5) × 1.15 = 20.93 Amps → Standard 30A or 60A Fused/Non-Fused Disconnect within sight.

Frequently asked questions

YES! Under NEC §240.4(G) and §440.6, HVAC branch circuits are exempt from the small conductor rules of §240.4(D). As long as the conductor ampacity meets or exceeds the nameplate MCA (e.g. 25A on #10 AWG) and the breaker does not exceed the nameplate MOCP (e.g. 40A), the installation is 100% code-compliant.

If the manufacturer equipment nameplate specifically states "Maximum Fuse Size" (rather than "Max Overcurrent Protective Device" or "Max Fuse or HACR Breaker"), NEC §110.3(B) requires the installation of a fused disconnect switch or fuse block rather than a standard circuit breaker.