How it works & the NEC rules behind it
Solar PV modules produce higher voltage in cold temperatures. Under NEC §690.7, the maximum photovoltaic system voltage must be calculated using the lowest expected ambient temperature to ensure system voltage never exceeds equipment ratings (e.g., 600V for residential dwellings per §690.7(C), or 1000V/1500V for commercial installations).
Key PV String Sizing Rules:
- 1. Cold-Weather Maximum Voc (§690.7(A)): Calculated using manufacturer temperature coefficients:
Max Voc = Voc(STC) × [1 + (Temp Coeff (%/°C) × (Lowest Temp °C − 25°C))].
Alternatively, Table 690.7(A) correction factors can be used. - 2. Maximum Panels per String:
Floor(Inverter Max DC Voltage ÷ Max Module Voc). Ensures the string never exceeds the inverter maximum voltage limit or 600V residential code cap. - 3. Minimum Panels per String (MPPT Tracking): Sized at high summer temperatures (e.g. +40°C to +65°C cell temp):
Ceil(Inverter Min MPPT Voltage ÷ High-Temp Vmp). - 4. DC Conductor & OCPD Sizing (§690.8): PV source circuits are subject to two 125% factors (125% for maximum current irradiance boost × 125% continuous duty = 156.25% of Isc):
Min Conductor Ampacity = Module Isc × 1.5625.