How it works & the NEC rules behind it
The National Electrical Code (NEC §210.52) mandates specific spacing rules for convenience receptacles in dwelling units so that standard 6-foot appliance cords can reach an outlet without dangerous extension cords.
The Core NEC Spacing Rules:
- 1. General Wall Space — The 6/12 Rule (§210.52(A)): In bedrooms, living rooms, and dens, receptacles must be installed such that no point along the floor line is more than 6 feet horizontally from an outlet. The maximum distance between two adjacent receptacles is 12 feet. Any wall segment 2 feet or wider requires an outlet.
- 2. Kitchen Countertops — The 2/4 Rule (§210.52(C)): Receptacles must be placed such that no point along the back wall line is more than 24 inches from an outlet (maximum 4 feet between outlets). Any countertop space 12 inches or wider requires an outlet.
- 3. Kitchen Islands & Peninsulas (§210.52(C)(2)): Must have at least one receptacle outlet, or a provision for a pop-up countertop assembly listed per UL 111 / §406.5(G).
- 4. Hallways (§210.52(H)): Any hallway measuring 10 feet or more in length must have at least one receptacle outlet.
- 5. Bathrooms (§210.52(D)): At least one 20A receptacle must be located within 36 inches of the outside edge of each sink basin.