Conduit & Cable Support Spacing Lookup

Lookup maximum support strapping intervals and distance from boxes for NM, MC, EMT, RMC, PVC, and FMC per NEC Chapters 3.

NEC edition

Inputs

ft

VoltageLab app

Take this toolkit with you on the job

The full VoltageLab electrician app — wire tables, code lookups and job-site calculators offline, on Android and iOS.

⚡ Test your knowledge
NEC Article 220 was renumbered in the 2026 code cycle. What is the new article number?
  • A. Art. 100
  • B. Art. 120
  • C. Art. 200
  • D. Art. 230
💡 NEC 2026 renumbered Article 220 (Branch-Circuit, Feeder, and Service Calculations) to Article 120.
Energy Management Systems were moved from Article 750 to which article in NEC 2026?
  • A. Art. 100
  • B. Art. 125
  • C. Art. 130
  • D. Art. 150
💡 NEC 2026 moved Energy Management Systems from Article 750 to Article 130.
Which NEC standard size overcurrent device comes after 90A?
  • A. 95A
  • B. 100A
  • C. 110A
  • D. 105A
💡 Per NEC §240.6(A), the standard sizes are …90, 100, 110, 125… There is no 95A standard size.

VoltageLab app

Studying for your electrical exam?

Practice NEC exam questions with full explanations and progress tracking, right on your phone.

How it works & the NEC rules behind it

Properly securing and supporting electrical cables and raceways prevents mechanical strain on terminals, sagging, and physical damage. The National Electrical Code (NEC Chapter 3) specifies precise maximum distances for fasteners, straps, and hangers.

Support Rules by Wiring Method:

  • NM-B (Romex, §334.30): Must be secured within 12 inches of every box/enclosure and at intervals not exceeding 4.5 feet (1.4 m).
  • Type MC Cable (§330.30): Must be secured within 12 inches of every box/fitting and at intervals not exceeding 6.0 feet (1.8 m). Cables with 4 or fewer conductors (≤ #10 AWG) can be fished without strapping.
  • EMT Conduit (§358.30): Must be fastened within 3 feet (900 mm) of every box, conduit body, or termination, and at intervals not exceeding 10 feet (3.0 m).
  • RMC / IMC Steel Conduit (§344.30): Fastened within 3 ft of boxes. Where made up with threaded couplings, straight horizontal runs permit spans from 10 ft (1/2"–3/4") up to 20 ft (3"+) per Table 344.30(B)(2).
  • PVC Conduit (§352.30): Fastened within 3 ft of boxes. Support spacing varies by trade size from 3 ft (1/2"–1") to 7 ft (4") per Table 352.30. Expansion fittings required where temperature variation exceeds 25°F.
  • Flexible Metal Conduit (FMC, §348.30): Fastened within 12 inches of box and every 4.5 feet.

Formulas & equations

Max Distance to First Box Strap ≤ 12" (Cables / FMC) or ≤ 3 ft (Conduit Raceways) Max Spacing Between Mid-Run Supports = Lookup from NEC Chapter 3 Article Total Straps Required = 1 + Ceil(Total Run Length ÷ Max Interval)

NEC reference table

Wiring Method / Conduit NEC Article Distance to Box / Fitting Max Interval Between Supports
NM-B (Romex)§334.3012 inches4.5 feet (54")
Type MC / AC Cable§330.3012 inches6.0 feet (72")
EMT (Thinwall Conduit)§358.303.0 feet (36")10.0 feet (120")
RMC / IMC (1"–1½")§344.303.0 feet (36")12.0 – 14.0 feet
RMC / IMC (3"+ Large)§344.303.0 feet (36")20.0 feet
PVC Conduit (½"–1")§352.303.0 feet (36")3.0 feet (36")
PVC Conduit (2"+)§352.303.0 feet (36")5.0 – 7.0 feet
FMC (Flexible Metal Conduit)§348.3012 inches4.5 feet (54")

Worked example, step by step

Example: Strapping an 80-Foot Run of 3/4" EMT Conduit

Setup: 80 ft straight horizontal run of 3/4" EMT between a panelboard and a disconnect.

  • 1. Distance from Boxes: Install first strap within 3.0 feet (36") of the panelboard, and last strap within 3.0 feet of the disconnect.
  • 2. Max Mid-Run Spacing: Per §358.30(A), maximum distance between supports is 10.0 feet.
  • 3. Strap Quantity: 1 (start) + Ceil(80 ft ÷ 10 ft) = 9 Straps / One-Hole Clamps Minimum.

Frequently asked questions

YES. Under NEC §330.30(B) Exception, Type MC cable is permitted to be fished between access points through concealed spaces in finished buildings without strapping, where securing is practically impossible.

Under NEC §358.30(A) Exception No. 1, where structural members do not readily permit fastening within 3 feet (such as open steel trusses), the distance from the box to the first support is permitted to be increased up to 5 feet (1.5 m).