According to the NEC, what is the required ampere rating for a motor disconnecting means that is disconnecting a motor with a full-load current (FLC) of 20A?
Per NEC 430.110(A), the disconnecting means must have an ampere rating of at least 115% of the motor full-load current rating (20A * 1.15 = 23A; standard rating 25A).
Question 2 of 10
Which term describes a motor control circuit that is tapped from the load side of the motor branch-circuit short-circuit and ground-fault protective device?
A motor control circuit carries the electric signals directing the performance of the controller but does not carry the main power current.
Question 3 of 10
For a stationary motor of 2 horsepower or less, what is permitted to serve as the disconnecting means?
NEC 430.109(A)(1) allows a branch-circuit breaker, general-use snap switch, or a plug-and-receptacle as a disconnecting means for motors 2 HP or less.
Question 4 of 10
When must a motor control circuit be provided with overcurrent protection?
Per NEC 430.72, overcurrent protection is required if the control circuit extends beyond the enclosure of the motor controller.
Question 5 of 10
What is the primary function of a motor 'controller' as defined in Article 100?
A controller is a switch or device that is normally used to start and stop a motor by making and breaking the motor circuit current.
Question 6 of 10
What is the maximum rating of an overcurrent protective device for a control circuit conductor with an ampacity of 15A that is protected by a 20A branch circuit breaker?
The overcurrent protection must not exceed the ampacity of the control circuit conductors (NEC 430.72(B)).
Question 7 of 10
Where must the disconnecting means for a motor be located relative to the controller?
NEC 430.102(A) requires the disconnecting means to be in sight from the controller location.
Question 8 of 10
The 'Full-Load Current' (FLC) rating of a motor is used for which of the following calculations?
The FLC (NEC Tables) is the standard value used for sizing conductors, disconnects, and protective devices.
Question 9 of 10
If a motor controller is 10 HP, which type of disconnecting means is required?
Motors over 2 HP require a disconnecting means that is horsepower-rated (NEC 430.109).
Question 10 of 10
What happens if a control circuit is tapped from the line side of the motor branch-circuit protective device?
If tapped from the line side, it is not protected by the motor branch-circuit OCPD and must have dedicated protection (NEC 430.72(A)).