Transformers are rated in kVA instead of kW primarily because:

Transformer losses (copper and iron losses) remain relatively constant irrespective of the load's power factor.
Question 2 of 5

What is the unit of measurement for transformer losses?

Transformer losses are expressed in VA or kVA.
Question 3 of 5

Copper losses in a transformer are primarily dependent on:

Copper losses are related to the square of the current (I²R).
Question 4 of 5

Iron losses in a transformer are primarily dependent on:

Iron losses are dependent on the voltage applied to the transformer.
Question 5 of 5

A transformer has a rating of 11 kVA. If the power factor of the load is 0.6, the output power will be:

Output power = kVA * Power Factor = 11 kVA * 0.6 = 6.6 kW