Conduit Fill Calculator β€” NEC Chapter 9 | VoltageLab
⚑ Electrical Calculator

Conduit Fill Calculator

NEC Chapter 9, Tables 1, 4 & 5 β€” EMT Β· IMC Β· RMC Β· PVC Β· THHN Β· XHHW Β· TW β€” Instant PASS/FAIL

πŸ“ Conduit & Conductors
Internal areas per NEC Chapter 9, Table 4
Wire areas per NEC Chapter 9, Table 5
Conductors in Raceway
AWG Size # Wires
Minimum Conduit Trade Size
β€”
β€”
Wire Area (inΒ²)
β€”
Conduit Area (inΒ²)
β€”
Fill %
βœ“ Check an Existing Conduit Size
Internal areas per NEC Chapter 9, Table 4
Wire areas per NEC Chapter 9, Table 5
Conductors in Raceway
AWG Size # Wires
PASS
β€”
Fill %
β€”
Wire Area (inΒ²)
β€”
Conduit Area (inΒ²)
Trade Size EMT (inΒ²) IMC (inΒ²) RMC (inΒ²) PVC 40 (inΒ²) PVC 80 (inΒ²)
1/2"0.3040.3420.3140.2850.217
3/4"0.5330.5860.5490.5080.409
1"0.8640.9590.8870.8320.688
1-1/4"1.4961.6471.5261.4531.237
1-1/2"2.0362.2252.0711.9861.711
2"3.4083.6303.4083.2912.874
2-1/2"5.8585.1354.8665.4524.119
3"8.8467.9227.4997.9226.605
3-1/2"11.54510.69410.01010.6949.210
4"14.75313.82712.88213.63111.850

Total cross-sectional areas per NEC 2023 Chapter 9, Table 4. Allowable fill: 40% for 3+ conductors, 31% for 2, 53% for 1 (NEC Chapter 9, Table 1). Multiply area Γ— fill % to get maximum conductor fill inΒ².

πŸ’‘
Need NEC code lookup on the job site?
VoltageLab's AI Code Lookup has every NEC article explained in plain English β€” searchable from your phone in seconds. Used by journeymen, masters, and exam candidates across the USA.

Based on NEC 2023 Chapter 9, Tables 1, 4 & 5. Fill limits: 40% (3+ conductors), 31% (2 conductors), 53% (1 conductor). Wire areas are for listed conductors per NEC Chapter 9, Table 5. Equipment grounding conductors and neutral conductors count toward fill. Results are indicative β€” always verify against the locally adopted NEC edition and consult a licensed electrician before installation.