HomeNEC ResourcesNEC CodeArticle 215 – Feeders

Article 215 – Feeders

Purpose

Article 215 of the National Electrical Code® (NEC®) establishes the requirements for the installation, sizing, and protection of feeder circuits — the conductors that carry power from the service equipment to branch circuit panels or distribution equipment.

Proper feeder design ensures safe power delivery without overheating or voltage drop.


Key Concepts

  1. Definition (215.2) A feeder is all circuit conductors between the service equipment (or separately derived system) and the final branch circuit overcurrent device.
  2. Conductor Sizing (215.2(A))
    • Feeders must have sufficient ampacity to handle the load served.
    • Continuous loads must not exceed 80% of the feeder rating (sized at 125% of the continuous load).
    • Apply voltage drop limits — feeders should not exceed 3% drop to maintain efficiency.
  3. Overcurrent Protection (215.3)
    • Feeders require overcurrent devices rated to protect conductors per their ampacity (Article 240).
    • Breakers or fuses must be located at the point where the feeder originates.
  4. Grounding & Bonding (215.6)
    • Feeder equipment grounding conductors (EGCs) must be sized per Table 250.122.
    • Grounded conductor (neutral) and EGC must be isolated in subpanels.
  5. Identification (215.12)
    • Feeder conductors must be color-coded or labeled to distinguish ungrounded, grounded, and grounding conductors.
    • Example:
      • Black, red, blue — phase conductors
      • White or gray — neutral
      • Green or bare — equipment ground
  6. Multiple Feeders & Disconnects (215.5)
    • Each feeder must have a main disconnecting means.
    • If multiple feeders supply one area, they must be clearly marked to show their source.
  7. Ground-Fault Protection (215.10)
    • Feeders supplying 800 A or more to 3-phase, 4-wire systems must include ground-fault protection.
    • This protects large equipment and minimizes service interruptions.

⚙️ Key Takeaways

  • Feeders carry large electrical loads — correct sizing and protection are critical.
  • Always follow ampacity tables (310.16) and protection rules (240).
  • Maintain clear identification, grounding, and disconnect labeling.
  • Voltage drop and overcurrent protection are essential for system performance and safety.
Md Nazmul Islam
Md Nazmul Islam
5+ years of experience in Android and iOS app development. Educational background in Electrical Engineering. Contributing to the EEE community through creative work at Voltage Lab. For any business development or discussion, feel free to follow and message me on LinkedIn (link below).

Recent Post