HomeNEC ResourcesNEC CodeNEC Table 430.250: Full-Load Currents for Three-Phase Motors

NEC Table 430.250: Full-Load Currents for Three-Phase Motors

This guide covers the application of NEC Table 430.250, which is used to determine the Full-Load Current (FLC) for three-phase alternating-current motors. This FLC value is critical for correctly sizing conductors, overcurrent protection, and motor control equipment.


📘 Table Purpose and Scope

NEC Table 430.250 provides standardized FLC values for motors running at usual speeds and with normal torque characteristics.

- Advertisement -
  • Voltage Ranges: The listed currents are for rated motor voltages but are also permitted for use within the system voltage ranges of 110 to 120 volts and 220 to 240 volts.
  • Application: The FLC found in this table must be used to determine the size of conductors and the rating of overcurrent protection devices, as mandated by NEC 430.6(A)(1), regardless of the actual measured current on the motor nameplate.

📊 NEC Table 430.250: Full-Load Currents (Three-Phase)

Horsepower115 Volts200 Volts208 Volts230 Volts460 Volts575 Volts2300 Volts
1/24.42.52.42.21.10.9
3/46.43.73.53.21.61.3
18.44.84.64.22.11.7
1-1/2126.96.66.03.02.1
213.67.87.56.83.42.7
31110.69.64.83.9
517.516.715.27.66.1
7-1/225.324.222119
1032.230.8281411
1548.346.2422117
2062.159.4542722
2578.274.8683427
309288804032
401201141045241
501501431306552
60177169154776216
75221211192967720
1002852732481249926
12535934331215612531
15041439636018014437
20055252848024019249
25060230224260
30072336128972
35083441433683
40047738296
450512410103
500579463116

💡 Application of FLC for Conductor Sizing

The FLC value found in Table 430.250 is used to determine the minimum size of the conductors supplying the motor.

Continuous Duty Motors (NEC 430.22(A)):

- Advertisement -

For a single motor used in a continuous duty application, the conductors must have an ampacity of not less than 125% of the motor’s FLC rating:

Minimum Conductor Ampacity = FLC (Table 430.250) x 1.25

This 125% increase accounts for the heat generated by continuous operation.

Example:

For a 10 HP motor operating at 460 Volts:

  1. Find FLC from Table 430.250: 14 Amperes.
  2. Calculate Minimum Ampacity: 14 A x 1.25 = 17.5 Amperes.
  3. You would then select a conductor size from NEC Table 310.16 that has an ampacity of at least 17.5 Amperes.

Note on Nameplate vs. Table:

Per NEC 430.6(A)(1), the FLC determined from this table must be used for sizing conductors and calculating the overcurrent protection rating, even if the FLC listed on the motor’s nameplate is different.

Md Nazmul Islam
Md Nazmul Islam
5+ years of experience in Android and iOS app development. Educational background in Electrical Engineering. Contributing to the EEE community through creative work at Voltage Lab. For any business development or discussion, feel free to follow and message me on LinkedIn (link below).

Recent Post