HomeNEC ResourcesGroundingEquipment Grounding Conductors (EGC)

Equipment Grounding Conductors (EGC)

What is the EGC?

The Equipment Grounding Conductor (EGC) is the primary safety mechanism of the electrical system.

While the Grounding Electrode Conductor (GEC) connects the system to the earth, the EGC connects all non-current-carrying metal parts (motor frames, outlet boxes, conduit) back to the main service panel.

- Advertisement -

The Two Main Jobs of the EGC:

  1. Safety: It ensures that metal parts do not stay energized if a hot wire comes loose.
  2. Tripping the Breaker: It creates a low-resistance path for fault current to flow back to the source, forcing the Overcurrent Protective Device (OCPD) (breaker or fuse) to trip immediately.

Permitted Types (NEC 250.118)

In the USA, the EGC isn’t always a wire. The NEC permits specific raceways to serve as the ground:

- Advertisement -
  • Wire: Copper or Aluminum (Bare, Green, or Green/Yellow striped).
  • Conduit: Rigid Metal Conduit (RMC), Intermediate Metal Conduit (IMC), and Electrical Metallic Tubing (EMT).
  • Note: Flexible Metal Conduit (FMC) has strict length limits to be used as a ground.

⚠️ Critical Warning: The Main Bonding Jumper

  • One Connection Only: The Neutral and the EGC are bonded together at only one point: the Main Service Disconnect.
  • The Component: This connection is made using the Main Bonding Jumper (MBJ). If this is missing, the breaker will NOT trip during a ground fault.
  • Never Downstream: Never connect Neutral and Ground together in sub-panels or outlets. This creates dangerous “ground loops.”

How to Size the EGC

Unlike the GEC (which is sized by wire size), the EGC is sized based on the rating of the Overcurrent Device (Breaker/Fuse) protecting the circuit.

NEC Table 250.122 Reference

Breaker / Fuse Rating (Amps)Copper EGCAluminum / Cu-Clad
15 A14 AWG12 AWG
20 A12 AWG10 AWG
30 A10 AWG8 AWG
40 A10 AWG8 AWG
60 A10 AWG8 AWG
100 A8 AWG6 AWG
200 A6 AWG4 AWG
300 A4 AWG2 AWG
400 A3 AWG1 AWG
500 A2 AWG1/0
600 A1 AWG2/0
800 A1/03/0
1000 A2/04/0
1200 A3/0250 kcmil
1600 A4/0350 kcmil
2000 A250 kcmil400 kcmil
2500 A350 kcmil600 kcmil
3000 A400 kcmil750 kcmil
4000 A500 kcmil1000 kcmil
5000 A700 kcmil1250 kcmil

3 Special Rules You Must Know

1. Voltage Drop Upsizing (NEC 250.122(B))

If you increase the size of your hot wires to account for voltage drop (long distance), you must increase the size of your EGC proportionately.

Example: If you double the circular mils of your hot wire, you must double the circular mils of your ground wire.

2. Parallel Conductors (NEC 250.122(F))

When running parallel conduits for large feeders:

  • The EGC must be installed in every raceway.
  • The EGC in each raceway must be full size based on the breaker rating. Do not divide the ground size by the number of conduits.

3. High-Fault Currents

In industrial settings where available fault currents exceed 10,000 Amperes, standard EGC sizing may not be sufficient. You may need to upsize the EGC to ensure it doesn’t melt before the breaker clears the fault.

⚠️ Critical Installation Rules (Must Read)

1. Voltage Drop Upsizing (NEC 250.122(B)) If you upsize the ungrounded (hot) conductors to reduce voltage drop, you must upsize the EGC proportionately.

Rule: The percentage increase in the EGC size must match the percentage increase of the hot wires.

2. Physical Protection (NEC 250.120(C))

  • Smaller than 6 AWG: Must be protected by a raceway or cable armor to prevent physical damage.
  • 6 AWG and larger: Can be run exposed if securely fastened to the surface.

3. Aluminum Restrictions (NEC 250.120(A)) Aluminum EGCs cannot be installed in direct contact with earth (dirt) or concrete (masonry), as they will corrode.

4. Flexible Metal Conduit (Flex) A separate wire-type EGC is required inside the flex if:

  • The circuit is over 20 Amps.
  • The flex length is greater than 6 feet (1.8m).

5. Parallel Conductors When running parallel conduits:

  • An EGC must be installed in each raceway.
  • It must be full size based on the breaker rating (do not divide the size).

6. Routing & Continuity

  • Routing: The EGC must be run within the same raceway or cable as the circuit conductors.
  • Splicing: Splices must be irreversible (crimp or exothermic weld).
  • Termination: Must be securely connected to the panel enclosure, bonding jumpers, and devices using approved terminals (NEC 250.8).

Examples of EGC Sizing and Calculations

Example 1: What is the suitable size of EGC for a 15 and 20 -Amp circuit breakers?

Solution:The rating of overcurrent devices used for the most common household applications are 15-amp and 20-amp.

Refereeing to the NEC table 250.122;

For 15-Amp Circuit

  • Copper EGC: 14 AWG
  • Aluminum / Copper-Clad Aluminum EGC: 12 AWG

For 20-Amp Circuit

Aluminum / Copper-Clad Aluminum EGC: 10 AWG

Copper EGC: 12 AWG

Example 2: What is the required size of EGC for a 60-Amp circuit breaker?

Solution:

  • OCPD Rating: 60 Amps
  • Referencing NEC Table 250.122:
    • Copper EGC: 10 AWG
    • Aluminum or Copper-Clad Aluminum EGC: 8 AWG
Md Nazmul Islam
Md Nazmul Islam
5+ years of experience in Android and iOS app development. Educational background in Electrical Engineering. Contributing to the EEE community through creative work at Voltage Lab. For any business development or discussion, feel free to follow and message me on LinkedIn (link below).

Recent Post