HomeNEC ResourcesNEC TablesProper Sizing of Conduits and Raceways. NEC Annex C.

Proper Sizing of Conduits and Raceways. NEC Annex C.

NFPA 731 Section 4.6.3.12(2) clearly states that whenever raceways, conduits, or tubing are used (even for security systems), they must be sized in accordance with the NEC®.

Improperly sized conduits can lead to:

- Advertisement -
  • Damaged insulation (abrasion) during pulling.
  • Overheating due to lack of air space.
  • Impossible future upgrades.

Which Table Do I Use?

The NEC provides two methods for calculating conduit fill. Knowing which one to use saves time.

1. The “Easy” Method: NEC Annex C

- Advertisement -

Use this when all conductors are the same size and insulation type (e.g., all 12 AWG THHN).

  • You simply look up the conduit size and wire size to find the max count.
  • Example: Table C.1 is for EMT, Table C.3 is for Flex (FMC).

2. The “Math” Method: NEC Chapter 9

Use this when you have mixed conductor sizes (e.g., three 12 AWG and two 6 AWG).

  • You must calculate the total cross-sectional area of all wires and ensure it doesn’t exceed 40% of the conduit’s internal area.

Reference: NEC Table C.1 (EMT)

Maximum Number of Conductors (THHN, THWN, THWN-2)

The table below shows the maximum number of same-size conductors allowed in Electrical Metallic Tubing (EMT).

Wire Size (AWG)½”¾”1″1 ¼”1 ½”2″
141222356184138
12916264561101
1051016283863
8369162236
6247121626
412471016
31136813
21135711
1111458

Note: This table applies only when all wires are the same size. If mixing sizes, you must perform a Chapter 9 calculation.

Md Nazmul Islam
Md Nazmul Islam
5+ years of experience in Android and iOS app development. Educational background in Electrical Engineering. Contributing to the EEE community through creative work at Voltage Lab. For any business development or discussion, feel free to follow and message me on LinkedIn (link below).

Recent Post