The board is off, the circuit is proven dead, and your low-resistance ohmmeter reads 0.24 Ω at the socket behind the sofa. Is that good? On its own the number means nothing. It only becomes a result when you know what the cable should read for its length and size, and whether every other socket on the ring reads about the same. That is the whole skill of a continuity test.
Continuity is the first dead test on any new circuit, and it is the one people rush. The leads aren’t nulled, a link goes on the wrong pair, or a reading from a parallel earth path through the pipework gets written down as R2. None of that shows up until the Zs reading doesn’t add up, or an assessor asks how you got the number. Done properly, the three-step ring test finds broken rings, interconnections and loose terminals before anyone plugs in a heater.
This guide covers what BS 7671 asks you to prove, the instrument you need, R1+R2 by method 1 and method 2, the full three-step ring final circuit test with a worked example, what the readings tell you, polarity, and where continuity sits in the sequence of tests.
Quick Answer
A continuity test proves, with the circuit isolated, that each conductor is unbroken and properly connected from end to end. Under BS 7671 Regulation 643.2.1 you must test the protective conductors of every circuit, including the main and supplementary bonding, and on a ring final circuit you must also test every live conductor of the ring. The usual result is R1+R2, the resistance of the line conductor plus the circuit protective conductor, measured with a low-resistance ohmmeter.
On a ring, you do it in three steps. First measure each conductor end to end. Then cross-connect line and neutral and check that every socket reads the same. Finally cross-connect line and cpc. The highest step 3 reading is the R1+R2 for the circuit.
Key Takeaways
- Continuity is a dead test. Safely isolate the circuit and prove it dead before you connect a lead.
- Use a low-resistance ohmmeter to BS EN 61557-4: 4 V to 24 V DC, at least 200 mA, with the leads nulled.
- Method 1 links line to cpc at the board and gives R1+R2 at every point. It also proves polarity.
- Method 2 uses a long wander lead from the MET and measures R2 only. It is the method for bonding conductors.
- On a healthy ring, r1 and rn agree within 0.05 Ω, and r2 is about 1.67 times r1 in 2.5/1.5 mm² cable.
- Step 2 and step 3 readings should be roughly the same at every socket. Readings that rise towards the middle mean the wrong ends are cross-connected.
- The R1+R2 value is added to Ze to predict Zs, which is then checked against the live loop test.
What a continuity test proves under BS 7671 Regulation 643.2
Regulation 643.2.1 requires a test of the continuity of conductors. That covers the protective conductors of every circuit, the main protective bonding conductors and any supplementary bonding conductors. On a ring final circuit it also covers the line and neutral conductors of the ring. The point is simple: an earth fault can only operate the protective device if there is a continuous, low-resistance path back to the main earthing terminal. A break, or a terminal that is barely gripping, leaves exposed metalwork live during a fault.

The instrument
Use a low-resistance ohmmeter, normally the continuity range of a multifunction tester, that meets BS EN 61557-4. It produces an open-circuit voltage of 4 V to 24 V DC and a short-circuit current of at least 200 mA. A multimeter’s beeper range does not meet this, and its readings are not acceptable on a certificate. Before every session, check the leads for damage, then null them: clip them together and zero the meter, so the resistance of the leads is not added to every reading.
Decoding R1, R2, r1, rn and r2
R1 is the resistance of the line conductor from the board to the furthest point of the circuit. R2 is the resistance of the circuit protective conductor (cpc) over the same run. Their sum, R1+R2, is what goes on the schedule of test results. Lower-case r1, rn and r2 are the end-to-end resistances of the line, neutral and cpc of a ring, measured with the ring opened at the board. Our note on the relationship between resistance and temperature explains why a reading taken cold is lower than the same cable at full load.
R1+R2 method 1 vs method 2 vs the ring test
Guidance Note 3 sets out two methods for protective conductors and a separate method for rings. They measure different things, so pick the one that fits the conductor you are proving.
| Method 1 | Method 2 | Ring final test | |
|---|---|---|---|
| Connection at the board | Line linked to cpc | Wander lead on the MET or cpc bar | Both ends of the ring, cross-connected |
| Measures | R1+R2 | R2 only | r1, rn, r2, then R1+R2 at each socket |
| Proves polarity too | Yes, at every point | No | Yes, at every socket |
| Best for | Radial circuits, lighting | Bonding conductors, cpcs of long runs | Every ring final circuit |
| Watch out for | Leaving the link on afterwards | Lead resistance; null it at full length | Cross-connecting the wrong pair |
Method 1 is quicker on a radial because one link at the board does the whole circuit. You probe line and earth at each point in turn, and the highest reading, usually at the furthest point, is R1+R2. Because you have to find the line conductor to get a reading, it also proves that every switch and fuse is in the line conductor. Method 2 is the one for main and supplementary bonding, where there is no line conductor to link to.
Parallel paths make a broken cpc look fine: on an installation with metal conduit, steel back boxes screwed to earthed metalwork or bonded pipes, the meter can find its way back to earth through the building rather than through the cpc. A cpc that is open at one terminal still gives a low, plausible reading. Where parallel paths are possible, disconnect the cpc at one end and test the conductor on its own, or check the reading against the expected value for the length and size. A reading much lower than the cable could possibly give is a warning, not a pass.
The ring final circuit test, step by step

The ring test proves three things at once: the ring is complete, it isn’t interconnected with another ring or bridged across itself, and every socket is connected to it properly. It gives you R1+R2 for the circuit along the way. Do it with the circuit isolated and both ends of the ring disconnected at the board.
- Isolate and prove dead. Lock off the circuit, prove your tester, prove dead and prove the tester again. Follow the safe isolation procedure in full.
- Identify the two ends. Disconnect both legs of line, neutral and cpc at the board, and mark one set as leg 1 and the other as leg 2.
- Step 1, end to end. Measure line to line (r1), neutral to neutral (rn) and cpc to cpc (r2) across the two legs. Write all three down.
- Check step 1. r1 and rn should be within 0.05 Ω of each other. In 2.5/1.5 mm² twin and earth, r2 should be about 1.67 times r1. In 2.5/2.5 cable, r2 should be about the same as r1.
- Step 2, line to neutral. Join L1 to N2 and N1 to L2. Measure between line and neutral at every socket on the ring. Each reading should be about (r1 + rn) ÷ 4, and all of them should be close to each other.
- Step 3, line to cpc. Remove those links. Join L1 to E2 and E1 to L2. Measure between line and earth at every socket. Each reading should be about (r1 + r2) ÷ 4. Record the highest as R1+R2 for the circuit.
- Check any spurs. A spur reads higher than the ring sockets by the resistance of its own cable, which is expected. A fused spur reads through its fuse, so check the fuse is fitted.
- Reconnect and record. Remove every link, reconnect the ring at the board, torque the terminals, and write r1, rn, r2 and R1+R2 on the schedule of test results.
A worked example
Take a 50 m ring in 2.5/1.5 mm² twin and earth. At 7.41 mΩ/m for 2.5 mm² and 12.10 mΩ/m for 1.5 mm², step 1 should give r1 ≈ 0.37 Ω, rn ≈ 0.37 Ω and r2 ≈ 0.61 Ω. Step 2 readings at every socket should be about (0.37 + 0.37) ÷ 4 ≈ 0.19 Ω. Step 3 readings should be about (0.37 + 0.61) ÷ 4 ≈ 0.25 Ω, so R1+R2 for the circuit is about 0.25 Ω. That is the 0.24 Ω from the opening paragraph. It is a good reading, because it matches what the cable should give and the other sockets agree with it.
The one that catches everyone: cross-connecting the same leg in step 2 or step 3. Join L1 to N1 and L2 to N2 instead of L1 to N2, and the readings no longer match. The sockets near the board read almost nothing and the ones in the middle of the ring read highest. If your readings climb towards the middle, don’t go looking for a fault in the ring. Check your links first, because the ring is probably fine and the cross-connection is wrong.
Expected values: conductor resistance per metre
To judge any reading you need the value the cable should give. Multiply the run length by the resistance per metre of the line and cpc together. The table gives the common combinations for copper at 20 °C.

| Conductor (mm²) | Resistance (mΩ/m) | Combination line/cpc | R1+R2 (mΩ/m) |
|---|---|---|---|
| 1.0 | 18.10 | 1.0 / 1.0 | 36.20 |
| 1.5 | 12.10 | 1.5 / 1.0 | 30.20 |
| 2.5 | 7.41 | 2.5 / 1.5 | 19.51 |
| 4.0 | 4.61 | 4.0 / 1.5 | 16.71 |
| 6.0 | 3.08 | 6.0 / 2.5 | 10.49 |
| 10 | 1.83 | 10 / 4.0 | 6.44 |
For a radial, the expected R1+R2 is simply length × R1+R2 per metre. A 20 m radial in 2.5/1.5 cable should read about 20 × 19.51 ÷ 1000 = 0.39 Ω. For a ring, the expected step 3 reading is a quarter of the end-to-end values added together, because the meter is measuring two halves of the ring in parallel. Add R1+R2 (corrected for temperature) to the measured Ze to predict Zs. The live earth fault loop test that follows should come out close to that figure, and a big gap between the two points to a bad joint you haven’t found yet.
Reading the results: a healthy ring vs a faulty one

What a pass looks like
- r1 and rn within 0.05 Ω of each other
- r2 in the right ratio to r1 for the cable used
- Step 2 and step 3 readings close to each other at every socket
- Spurs reading a little higher than the ring sockets, by about the resistance of their own cable
- R1+R2 close to the value expected from the cable length and size
What each fault looks like
- Open circuit end to end on any conductor: the ring is broken, so it is really two radials. Each leg may then be undersized for the 32 A device.
- r1 and rn far apart: a high-resistance joint or a loose terminal on the conductor with the higher reading.
- Step 2 or 3 readings rising towards the middle: the cross-connection is on the same leg. Fix the links and repeat.
- Readings lower than the cable could give: the ring is interconnected with another ring, or bridged across itself somewhere.
- One socket much higher than the rest: a poor termination at that socket, or it is on a spur you didn’t know about.
- No reading at a socket: a broken conductor, or line and neutral reversed at that socket so you are measuring the wrong pair.
Polarity
Regulation 643.6 requires a polarity test to show that every fuse and single-pole control or protective device is in the line conductor only, that the centre contact of Edison screw lampholders is connected to line (except E14 and E27 lampholders to BS EN 60238), and that socket-outlets and similar accessories are correctly connected. Method 1 and step 3 of the ring test do this for you. If you get a reading between line and earth at a socket or a switch, line is where it should be. On a lighting circuit, operate each switch during the test so you prove the switch line as well.
Continuity vs the other dead and live tests
| Order | Test | Dead or live | What it proves |
|---|---|---|---|
| 1 | Continuity of protective and ring conductors | Dead | Unbroken conductors; gives R1+R2 |
| 2 | Insulation resistance | Dead | No leakage between conductors or to earth |
| 3 | Polarity | Dead (confirmed live) | Switches and devices in the line conductor |
| 4 | Earth electrode resistance (TT) | Live | Electrode gives a low enough RA |
| 5 | Earth fault loop impedance (Ze, Zs) and PFC | Live | Devices disconnect in time; confirms R1+R2 |
| 6 | RCD and AFDD operation, functional tests | Live | Protective devices and controls work |
Continuity comes first for a reason. If the cpc is broken, every later test relies on a protective path that isn’t there, and a live test could leave metalwork live during a fault. The order follows Section 643 of BS 7671. For why the earth path matters so much, see the importance of earthing rules and our guide to earthing cable size calculation. The device that the R1+R2 has to satisfy is covered in the types of MCB. If you are chasing a fault the ring test turned up, our explainer on open, short and closed circuits covers the patterns.
Method 1 or method 2: which should you use?
Method 1: pros
- Gives R1+R2 directly, the figure the schedule asks for.
- Proves polarity at every point in the same pass.
- Needs no long lead, so it is quick on a radial.
Method 1: cons
- Useless for bonding conductors, which have no line conductor to link.
- The link at the board is easy to forget, and it leaves a dead short to earth when you re-energise.
Use method 1 on radial circuits and lighting, and the three-step test on every ring. Keep method 2 for main and supplementary bonding, and for proving a cpc on its own when you suspect a parallel path. Many testers use both on the same job, and there is nothing wrong with that as long as the schedule records which value is which.
Continuity testing in the field
Do
- Null the leads before each session, and at full length for a wander lead.
- Work out the expected reading before you start.
- Use a socket adaptor or plug-in test lead so every socket is tested the same way.
- Operate every switch on lighting circuits during the test.
- Remove every link and reconnect before insulation testing.
Avoid
- Using a multimeter beeper as your continuity instrument.
- Accepting a reading far lower than the cable could give.
- Cross-connecting the same leg in steps 2 and 3.
- Recording only the end socket instead of the highest reading.
- Testing a circuit you haven’t proved dead.
Practise the readings before the assessment
VoltageLab: Electrician App has a testing practice shelf built on BS 7671, with continuity, ring final, insulation resistance and polarity questions that make you work out the expected reading and spot the fault. Choose BS 7671 as your standard when you open it.
Frequently asked questions
What is a good R1+R2 reading?
One that matches the value expected from the cable size and length. Multiply the length by the R1+R2 per metre for the cable. Then check that Ze plus R1+R2, corrected for temperature, stays below the maximum Zs for the protective device.
Why is r2 higher than r1 on a ring?
In 2.5/1.5 mm² twin and earth the cpc is smaller than the line conductor, so it has more resistance per metre. The ratio is 12.10 ÷ 7.41, about 1.67.
Why divide by four in the ring test?
After the cross-connection, the meter sees two loops in parallel, each made of half the line conductor and half the other conductor. Half the length gives half the resistance, and two equal paths in parallel halve it again, so each reading is about a quarter of r1 plus rn (or r1 plus r2).
Can I do a continuity test with a multimeter?
Not for certification. The instrument must meet BS EN 61557-4, with an open-circuit voltage of 4 V to 24 V DC and a test current of at least 200 mA. A multimeter’s continuity range doesn’t meet that and can’t reliably show a high-resistance joint.
What does the polarity test check?
That every single-pole switch, fuse and protective device is in the line conductor, that Edison screw lampholder centre contacts are on line (apart from E14 and E27 to BS EN 60238), and that sockets are wired correctly. Method 1 and the ring test prove it as you go.
What should main bonding read?
BS 7671 gives no single maximum, but a sound main bonding conductor of normal length will read a very low value, typically 0.05 Ω or less, measured end to end with method 2. A reading much higher than that points to a poor clamp or a corroded connection.
Do I need to test continuity on an EICR?
Yes, on a sample of circuits agreed with the client at least, and on every circuit where you have reason to doubt the protective conductor. Continuity of the main bonding should always be checked.
The bottom line
A continuity test is only as good as the number you compare it with. Know the cable’s resistance per metre, work out the expected R1+R2 before you start, and use the three-step test on every ring so a broken leg, an interconnection or a loose terminal can’t hide. Done that way, the reading on the schedule means something, and the live loop test that follows should simply confirm it.
Two habits stop most mistakes. Null your leads, and check every cross-connection before you blame the ring. Before any of it, carry out the safe isolation procedure, and for the wider picture of why the protective path has to be continuous, see grounding and bonding essentials.