NEC Residential Load Calculator
NEC Article 220 Standard Method β Dwelling service sizing with demand factors for lighting, appliances, HVAC & EV chargers
General lighting demand: first 3,000 VA @ 100%, next 117,000 VA @ 35%, balance @ 25%. Non-coincident A/C vs. heating β larger used. Results at 240V single-phase service.
General lighting: 3 VA/ftΒ² β NEC Table 220.12. Small appliance and laundry circuits: 1,500 VA each β NEC 220.52. Demand factors: first 3,000 VA @ 100%, next 117,000 VA @ 35%, balance @ 25% β NEC 220.42. Fixed appliances: 75% demand if 4+ units β NEC 220.53. Ranges: Column C demand β NEC Table 220.55. Dryers: 5 kW min/unit β NEC Table 220.54. HVAC: non-coincident loads β NEC 220.60. Total VA Γ· 240V = minimum service amps. Results are indicative β always verify with a licensed electrician before permit submission.