Fault Current Calculator

NEC 110.9 · Available Short Circuit Current · Point-to-Point Method · AIC Rating

⚙️ System Configuration
🔌 Upstream Source
📐 Conductor Run to Equipment

Set length to 0 to calculate fault current at the transformer secondary only (no conductor run reduction).

🔍 Equipment AIC Check — optional
Please fill in all required fields.
RESULT
At Transformer
Secondary (kA)
At Panel /
Equipment (kA)
Min AIC Rating
Required (kA)
💡
Need NEC code lookup on the job site?
VoltageLab's AI Code Lookup has every NEC article explained in plain English — searchable from your phone in seconds. Used by journeymen, masters, and exam candidates across the USA.

Transformer secondary (3Φ): I = (kVA × 1,000) / (√3 × V × Z%)  |  Single-phase: I = (kVA × 1,000) / (V × Z%)
Point-to-point (3Φ): Zcable = R(Ω/kft) × L / 1,000 per phase; Ifault = VLN / (Zsource + Zcable)
Point-to-point (1Φ): Zcable = 2 × R(Ω/kft) × L / 1,000; Ifault = V / (Zsource + Zcable)
Conductor resistance from NEC Chapter 9, Table 9 (75°C, PVC conduit). Bolted fault (worst-case) assumption. Always verify with a licensed electrical engineer before installation.