Motor Branch Circuit Calculator
NEC Article 430 · Conductors (430.22) · Protection (430.52) · Overloads (430.32) · EGC (250.122) · Tables 430.248 & 430.250
Most general-purpose motors have SF ≥ 1.15. Check nameplate.
Inverse-time breakers and dual-element fuses are most common for motor circuits.
Conductor
Max Size
Relay Max
Size
Branch conductor: NEC 430.22 — ampacity ≥ 125% × FLC | Protection: NEC 430.52 — max rating per Table 430.52 % × FLC, next standard size up | Overload: NEC 430.32 — 125% (SF ≥ 1.15) or 115% (others) | EGC: NEC Table 250.122 based on OCPD rating
FLC from NEC Table 430.248 (single-phase) or Table 430.250 (three-phase) per NEC 430.6(A)(1) — nameplate current not used for circuit sizing.
Standard device sizes per NEC 240.6(A). Results are indicative. Verify with a licensed electrical engineer before installation.