BS7671 Cable Sizing Calculator
18th Edition · Appendix 4 · Reference Methods A–F · Ca × Cg × Ci Correction Factors · Voltage Drop per Regulation 525.1
The actual current the circuit will carry under normal operation.
In ≥ Ib required. Cable must carry In: Iz ≥ In.
Method B: In conduit on wall, enclosed trunking, or cable duct — standard for most UK domestic installations.
70°C PVC is standard T&E, SWA. 90°C XLPE has ~10–15% higher rating.
Standard is 30°C in air, 15°C in ground. Lofts and boiler rooms often exceed 40°C.
Cables touching insulation or buried within it require Ci derating.
Current ratings from BS7671:2018+A2:2022 Appendix 4 Tables 4D2A / 4E2A (Cu, PVC/XLPE multicore, in air). Buried values from Table 4D5A (soil resistivity 2.5 K·m/W).
Formula: Iz = It × Ca × Cg × Ci ≥ In ≥ Ib. Minimum required It = In ÷ (Ca × Cg × Ci). Voltage drop per Appendix 4 mV/A/m tables.
90°C XLPE ratings approximate (Table 4E2A × ~1.08–1.17 vs 70°C PVC). For Method D, single-circuit values — no Cg applies. Results are indicative — always verify calculations with a qualified electrical engineer.
