Wire Size / Ampacity Calculator

NEC Table 310.16 — Copper & Aluminum · 60/75/90°C · Conduit derating per NEC 310.15(B)(3)

⚙️ Circuit Parameters
Aluminum min: 12 AWG — use AL-rated terminations
Most equipment terminals are 75°C rated — use 75°C column unless terminations are verified 90°C per NEC 110.14(C)
NEC 310.15(B)(3) — Neutral conductors carrying only unbalanced current and EGCs do not count
Please enter a valid load current greater than zero.
Minimum Conductor Size
Table Ampacity
Derated Ampacity
Max OCPD
✓ Verify an Existing Wire Size
Please select a wire size and enter a valid load current.
PASS
Load Current
Table Ampacity
Derated Ampacity
Size Cu 60°C Cu 75°C Cu 90°C Al 75°C Max OCPD (Cu 75°C)
14 AWG15 A20 A25 AN/A15 A *
12 AWG20 A25 A30 A20 A20 A *
10 AWG30 A35 A40 A30 A30 A *
8 AWG40 A50 A55 A40 A50 A
6 AWG55 A65 A75 A50 A60 A
4 AWG70 A85 A95 A65 A80 A
3 AWG85 A100 A115 A75 A100 A
2 AWG95 A115 A130 A90 A110 A
1 AWG110 A130 A145 A100 A125 A
1/0125 A150 A170 A120 A150 A
2/0145 A175 A195 A135 A175 A
3/0165 A200 A225 A155 A200 A
4/0195 A230 A260 A180 A225 A
250 kcmil215 A255 A290 A205 A250 A
300 kcmil240 A285 A320 A230 A275 A
350 kcmil260 A310 A350 A250 A300 A
400 kcmil280 A335 A380 A270 A325 A
500 kcmil320 A380 A430 A310 A375 A

* NEC 240.4(D) hard limits: 14 AWG Cu = 15 A max, 12 AWG Cu = 20 A max, 10 AWG Cu = 30 A max. Max OCPD shown is the largest standard breaker size at or below the 75°C ampacity. Assumes ambient 30°C, 3 or fewer CCC.

💡
Need NEC code lookup on the job site?
VoltageLab's AI Code Lookup has every NEC article explained in plain English — searchable from your phone in seconds. Used by journeymen, masters, and exam candidates across the USA.

Based on NEC Table 310.16 (2023 NEC) — allowable ampacities for insulated conductors rated 0–2000V, in a raceway or cable, ambient 30°C (86°F). Derating per NEC 310.15(B)(3). Max OCPD per NEC 240.4 and 240.4(D). Results are indicative — always verify against the locally adopted NEC edition and consult a licensed electrician before installation.