Fault Current Calculator
NEC 110.9 · Available Short Circuit Current · Point-to-Point Method · AIC Rating
Set length to 0 to calculate fault current at the transformer secondary only (no conductor run reduction).
Secondary (kA)
Equipment (kA)
Required (kA)
Transformer secondary (3Φ): I = (kVA × 1,000) / (√3 × V × Z%) | Single-phase: I = (kVA × 1,000) / (V × Z%)
Point-to-point (3Φ): Zcable = R(Ω/kft) × L / 1,000 per phase; Ifault = VLN / (Zsource + Zcable)
Point-to-point (1Φ): Zcable = 2 × R(Ω/kft) × L / 1,000; Ifault = V / (Zsource + Zcable)
Conductor resistance from NEC Chapter 9, Table 9 (75°C, PVC conduit). Bolted fault (worst-case) assumption.
Always verify with a licensed electrical engineer before installation.