Transformer Sizing Calculator
NEC 450 · IEC 60076 · KVA Sizing · Full Load Amps · OCPD Guidance
Primary voltage is optional — used to calculate primary full-load amps and NEC 450.3 OCPD sizing.
(kVA)
(kVA)
to Specify (kVA)
Single-phase: kVA = (V × I) / 1,000 | Three-phase: kVA = (√3 × V × I) / 1,000
From kW: kVA = kW / PF | FLA = (kVA × 1,000) / V (1Φ) or (kVA × 1,000) / (√3 × V) (3Φ)
NEC 450.3(B): Primary OCPD ≤ 125% × primary FLA (for FLA ≥ 9 A). Standard sizes per NEC 240.6(A).
For non-linear loads (VFDs, UPS, computers), apply additional K-factor derating — consult transformer manufacturer.
Results are indicative. Always verify with a licensed electrical engineer before specifying equipment.