NEC Fuse Sizing Calculator

Overcurrent Protection Selector Β· NEC 240.4 Β· Round-Up Rule (240.4(B)) Β· Small Conductor Caps (240.4(D)) Β· Standard Sizes (240.6(A))

βš™οΈ Conductor Selection

Multi-receptacle branch circuits cannot use the round-up rule per NEC 240.4(B)(1).

Continuous Load
Operating 3+ hours (NEC 210.20(A) β€” max load = 80% of OCPD)
Please fill in all required fields.
RESULT
β€”
Conductor Ampacity
β€”
Max OCPD
β€”
Continuous Load Max
πŸ“Š Step-by-Step β€” NEC 240.4 Logic
πŸ“‹ NEC 240.4 Quick Reference β€” Max OCPD by Conductor Size
Conductor Cu Ampacity
(75Β°C)
Cu Max OCPD
(General)
Al Ampacity
(75Β°C)
Al Max OCPD
(General)

240.4(D) cap shown in amber β€” applies to 14, 12, and 10 AWG copper only. General circuit (not multi-receptacle). Terminal rating 75Β°C. NEC 240.6(A) standard sizes applied.

πŸ’‘
Need NEC Article 240 on the job?
VoltageLab's AI Code Lookup has every NEC Article 240 section β€” overcurrent device sizing, conductor protection, fuse and breaker ratings, and the small conductor rules β€” referenced and explained instantly. Stop hauling a codebook to every panel.

Ampacity from NEC Table 310.16 (conductors in raceway or cable, not more than 3 current-carrying conductors, 30Β°C ambient). Terminal temperature limits per NEC 110.14(C).
Round-up rule: NEC 240.4(B) β€” permitted for general circuits where result ≀ 800A and conductor ampacity does not correspond to a standard size. Not permitted for multi-receptacle branch circuits.
240.4(D) caps apply to copper only: 14 AWG = 15A max, 12 AWG = 20A max, 10 AWG = 30A max. Standard OCPD sizes per NEC 240.6(A).
Results are indicative. Always verify with a licensed electrical engineer. Local codes may impose additional restrictions.